Cast-in passive fire protection

The cast-in fire collar for pipe penetrations in concrete slabs

Designed into the slab before the pour. In a fire, patented springs snap the seal shut, stopping flame and smoke between floors.

  • LPCB certified
  • Slabs 150mm thick and up
  • Patented spring activation
Sure Snap cast-in fire collar range: H110S, H65S and H150S
Find the right collar

The Sure Snap cast-in fire collar range

Sure Snap H65S cast-in fire collar

H65S

Ø up to 63mm

For small-bore pipes, such as appliance and branch wastes.

PVCPPHDPE

LPCB Certified

Sure Snap H110S cast-in fire collar

H110S

Ø up to 110mm

For standard plastic pipes, such as soil pipes and waste stacks.

PVCPPHDPE

LPCB Certified

Sure Snap H150S cast-in fire collar

H150S

Ø up to 160mm

For large-bore pipes, such as main stacks and risers.

PVCPPHDPE

LPCB Certified


Accessories


Sure Snap 110mm cast-in collar height extension

Extensions

Stackable 50mm rings for slabs thicker than 250mm.

Fits all collar sizes

View Extensions →

Sure Snap 110mm Manifold Recess Former

Manifold Recess Former

Recesses an H110S collar to support a pipe manifold.

For use with H110S

View the Manifold Recess Former →

All collars are LPCB-approved (Cert 1833a).

View the certification →

Sure Snap fire collar cast into the reinforced deck at The Rushgroves

Installation essentials

Designed for a fast, clean cast-in install

  • Cast-in. Fixed to the formwork, with the aid of the locator plate, which also blocks slurry. Sits flush with the underside of the slab.
  • Collar height. 250mm as standard. Trim the top to slab level on site if needed, or stack 50mm extensions for slabs thicker than 250mm.
  • Manifolds (H110S). Where a manifold sits on the slab, the H110S can be recessed using the approved Manifold Recess Former.
  • Built for the site. Snap-off points make striking formwork easy. The removable cap withstands heavy site traffic, and the bright casing is easy to spot on a busy deck.

Drawings, ratings and certification →

How it works

How a Sure Snap collar seals a penetration

Where a plastic pipe passes through a fire-rated floor, it becomes an opening in an otherwise sealed element. In a fire, the pipe melts and burns away, leaving an open hole for flame and smoke to spread between floors.

A Sure Snap collar closes that hole and restores the floor’s fire resistance where the pipe passes through it. Because smoke, not flame, causes most high-rise fire deaths, sealing the opening fast is what counts. Sure Snap is built to stop both.

See the installation guide →

Sure Snap collar cast into a concrete slab, before the pipe is fitted

01


Before the pour

Cast into the slab

Fixed to the formwork and secured in the slab with steel pins.

Plastic pipe installed through a cast-in Sure Snap collar

02


In service

Pipe runs through the slab

The plastic pipe runs through the collar, which stays dormant through normal service, ready to act.

Cutaway of a Sure Snap collar showing the intumescent lining that seals the pipe in a fire

03


In fire

The seal snaps shut

Fusible links melt and release the springs, compressing the Intumesh™ intumescent around the collapsing pipe.

See it in action

See why Sure Snap is the premium choice

We put a Sure Snap collar in a side-by-side fire test against a competitor’s fire collar. Sure Snap’s patented spring activation and the Intumesh™ intumescent deliver a fast-closing seal, stopping flame and smoke from escaping through the pipe.

Case studies

Trusted on major UK developments

Woodberry Down, London

Berkeley Group

Sure Snap cast-in collars were used to firestop plastic-pipe penetrations through the floor slabs on one of London’s largest residential regeneration schemes, installed in the formwork as each floor was poured.

Third-party certified and specified

NBS Source listed
Association for Specialist Fire Protection member