Cast-in fire collar
H65S 65 mm cast-in fire collar
The smallest collar in the range, sized for small bore plastic pipe penetrations up to 63 mm, such as appliance and branch wastes. Cast into the slab before the pour and sealed by patented spring activation, restoring the floor’s fire resistance where a pipe passes through it.


Installation essentials
Designed for a fast, clean cast-in install
What’s inside
What’s inside the H65S
A closer look at the components that make up the H65S and what each one does.

- Cap. The centre is punctured, then the cap is pried out with a screwdriver.
- Extension. Each one adds 50 mm of height.
- Collar casing. The rigid polypropylene body.
- Rubber ring. Seals against the pipe.
- Spring pocket. Houses the activation springs.
- Intumescent lining. The patented Intumesh that expands in a fire.
- Base flange. Prevents concrete ingress and gives clip points to align adjacent collars.
- Locator plate. A grooved plate that holds the pipe in place, with a central fixing hole and alignment windows.
Specifications
H65S specifications
| Stock code | SELFC-H65S |
| Nominal pipe Ø | Up to 63 mm (small-bore pipes) |
| Inner Ø | 84 mm |
| Standard collar height | 250 mm (trim on site; 50 mm extensions) |
| Base flange | 168 mm round |
| Casing | Polypropylene, 1.6 mm wall |
| Activation springs | 3, galvanised steel with nylon fuse links |
| Intumescent | Patented Intumesh, mesh backed sheet |
| Minimum slab thickness | 150 mm |
| Minimum concrete strength | 20 MPa |
| Accessories | Connection Clips, stackable extensions |
| LPCB certificate | 1833a/01 |
Fire performance
Tested fire resistance by pipe type
All figures are from the BRE Extended Application Report P104650-1003 Issue 3. The last two columns are the EN 13501-2 classifications: insulation (EI) is how long the collar holds back both heat and flame, and integrity (E) is the longer period it keeps stopping flame and hot gases.
Up to 4 hrs
PP bell end pipe, tested to BS EN 1366-3.
| Pipe type | Diameter (mm) | Pipe wall (mm) | End / socket wall (mm) | Insulation (EI) | Integrity (E) |
|---|---|---|---|---|---|
| PVC | 40 to 63 | 3.3 to 5.1 | 180 min | 240 min | |
| PVC with socket | 40 to 63 | 3.5 to 5.0 | 3.5 to 5.0 | 180 min | 240 min |
| PP | 40 to 50 | 2.2 to 2.3 | 180 min | 240 min | |
| PP with bell end | 40 to 50 | 1.8 to 2.7 | 1.8 to 2.7 | 180 min | 240 min |
| PE-HD | 26 to 64 | 3.0 to 6.4 | 120 min | 240 min | |
| PE-X | 16 to 63 | 3.1 to 9.7 | 90 min | 90 min |
Swipe to see all columns →
Manufacturer compatible pipes
The ratings above are certified by generic pipe type (PVC, PP, PE-HD, PE-X). Sure Snap also lists the following materials and branded systems as compatible (manufacturer information). Confirm the certified rating for your specific pipe and configuration against the certification and EN Global Compliance Report, and reach out to our technical team if you need clarification.
Materials
U-PVCP-PVCC-PVCHDPEMDPEABSPP-RPE-X
Branded systems
Rehau Raupiano PlusValsir TriplusAkatherm dBlue
Documentation
Compliance and downloads
Third party tested by BRE Global.
LPCB approved (1833a/01) and listed on NBS Source.
Drawings, CAD and BIM files
Resources
Sealing the annular gap (top of slab, per BRE Issue 3)
| Up to 10 mm | No backfill required |
| 10 to 20 mm | Sika Everbuild Everflex LMA 200 Contractors Sealant, 10 mm deep |
| 20 to 40 mm | Weber Saint Gobain non shrink grout over a cardboard gasket |
PP pipes also take a PE foam strip (about 5 × 30 mm) around the pipe. Full method in the installation guide.
See it in action
Outperforms a competitor’s collar
We put a Sure Snap collar in a side by side fire test against a competitor’s fire collar. Sure Snap’s patented spring activation and the Intumesh™ intumescent deliver a fast closing seal, stopping flame and smoke from escaping through the pipe.
Complete the system
Accessories and related products
Accessories for the H65S
Other collar sizes
Spares
Reinforced removable caps and anti slurry locator plates are available separately for every collar size.