Cast-in fire collar
H110S 110mm Cast-in Fire Collar
The most commonly specified collar in the range, sized for 110mm soil pipes, waste stacks and other plastic pipe penetrations. Cast into the slab before the pour and sealed by patented spring activation, restoring the floor’s fire resistance where a pipe passes through it.

Fire performance
Tested fire resistance by pipe type
All figures are from the BRE Extended Application Report P104650-1003 Issue 3. The last two columns are the EN 13501-2 classifications: insulation (EI) is how long the collar holds back both heat and flame, and integrity (E) is the longer period it keeps stopping flame and hot gases.
EN 13501-2
Tested to BS EN 1366-3. See the table for your pipe and configuration.
| Pipe type | Diameter (mm) | Pipe wall (mm) | End / socket wall (mm) | Insulation (EI) | Integrity (E) |
|---|---|---|---|---|---|
| PVC | 55 to 110 | 2.0 to 7.2 | 180 min | 180 min | |
| PVC with socket | 50 to 110 | 2.0 to 7.3 | 2.0 to 7.0 | 180 min | 180 min |
| PP | 50 to 110 | 2.1 to 3.8 | 120 min | 180 min | |
| PP with bell end | 50 to 110 | 2.2 to 3.8 | 2.2 to 3.8 | 180 min | 240 min |
| PE-HD | 50 to 110 | 3.4 to 10.9 | 120 min | 120 min |
Swipe to see all columns →
Manufacturer-compatible pipes
The ratings above are certified by generic pipe type (PVC, PP, PE-HD). Sure Snap also lists the following materials and branded systems as compatible (manufacturer information). Confirm the certified rating for your specific pipe and configuration against the certification and EN Global Compliance Report, and reach out to our technical team if you need clarification.
Materials
U-PVCP-PVCC-PVCHDPEMDPEABSPP-R
Branded systems
Rehau Raupiano PlusValsir TriplusAkatherm dBlue
Specifications
H110S specifications
| Stock code | H110S-RR |
| Inner Ø | 138mm |
| Standard collar height | 250mm (trim on site; 50mm extensions) |
| Base flange | 194 × 184mm rectangular |
| Casing | Polypropylene |
| Activation springs | 4 made of galvanised steel |
| Intumescent | Patented Intumesh, mesh-backed sheet |
| Accessories | Manifold Recess Former, stackable extensions |
| LPCB certificate | 1833a/03 |
Documentation
Compliance and downloads
Third-party tested.
LPCB approved (1833a/03) and listed on NBS Source.
Drawings, CAD and BIM files
Resources
Sealing the annular gap (top of slab, per BRE Issue 3)
| Up to 10mm | No backfill required |
| 10 to 20mm | Sika Everbuild Everflex LMA 200 Contractors Sealant, 10mm deep |
| 20 to 40mm | Weber Saint Gobain non shrink grout over a cardboard gasket |
PP pipes also take a PE foam strip (about 5 × 30mm) around the pipe. Full method in the installation guide.